Field Reports & Operator Notes
Testimonials and extended case notes from cooling-path assessments on mining facilities rated 0.05 PH/s and above in South Korea.
Operator testimonials
“Our 0.09 PH/s hall had two rows that throttled every afternoon. Page Sequoiacore traced hot air curling from the ceiling return into the front aisle. The baffle fix cost less than one month of lost hash we had accepted as normal.”
— Ji-hoon Lee, hall manager, Suwon co-location
“I wanted a shorter report. They delivered forty pages. Still, the shroud gap photos on rack C14 convinced my board to fund duct sealing before we ordered more S19 units.”
— Yoon-seo Kang, private operator, Gangnam
“The thermal survey caught a dry cooler branch flowing half the rate of its neighbor. Our plumber fixed it in a day. I wish the memo had included part numbers for the balancing valves they recommended.”
— Dong-min Yeo, immersion farm, Paju
“Airflow consultation before our second hall saved us from mirroring the first hall’s mistake — exhaust fans pushing against a dead plenum. Not cheap, but cheaper than retrofitting later.”
— Soo-jin Baek, facilities lead, Seongnam
Case note: Gyeonggi private farm (0.07 PH/s)
Situation: Operator reported gradual hash-rate decline over six weeks without obvious hardware faults. Internal team replaced PSUs and reseated boards with no lasting improvement.
Assessment focus: Cooling-path trace on four rack rows, inlet logging at 15-minute intervals during afternoon peak.
Finding: Rear exhaust panels mounted flush against a wall with only 8 cm clearance. Hot air pooled and recirculated into the cold aisle via a ceiling gap above row two.
Remediation: Relocated panels 25 cm forward, added deflector plates, sealed ceiling penetration. Operator reported stable hash through the following summer intake season.
Follow-up: Six-month thermal survey showed inlet delta reduced from 14°C above ambient to 6°C.
Case note: Incheon co-location hall (0.15 PH/s)
Situation: Tenant onboarding required third-party thermal documentation before insurance renewal.
Assessment focus: Thermal imaging survey across 72 rack faces plus spot cooling-path checks on highest-density tenant zones.
Finding: Three tenants within spec; one tenant’s custom shrouds left 12 mm gaps at hash board edges, creating streak hot spots on IR maps.
Remediation: Tenant replaced shrouds using our annotated images as acceptance criteria. Co-location used the report template for future tenant technical requirements.